247 The GOLDEN FILE of
NuMI BEAM PERMIT SYSTEM INPUTS
Sample Time Key:    Cont = SAT1 = Continuous at 5 Hz   BE = SAT2 = $25 Before Extraction
AE = SAT3 = 6 msec After Extraction (TD0)   JBE = SAT4 = Just Before Extraction  (Various TD1s)
BJBE = SAT5 = Beam Cycle Just Before Extraction (TD2)
10-Aug-05
10:00 AM
Ref # Item ACNET Name 200 PCI MADC
-CHAN
Sample   Time Requirement for Permit Anticipated
Nominal
Anticipated
Low Trip
Anticipated
High Trip 
Programmed
Low Trip 
Programmed
High Trip 
Full Scale Value
at MADC
NOTE This Color Indicates Input Has Been Masked.
60S "60S" C204 for MADC #65 at CC $63 N21.   SAT1 SAT2 SAT3 SAT4  Required Here.
SAT4 Should Finish Just Before MIBS $74.
60S-1 Extraction Kicker PS Charging Waveform Reference I:KPS6NF X 65-5 BE
SAT2
Charging Waveform Refererence Nominal 50.001 kVolts Nom - 5% Nom + 5% 47.5 52.5 60 kVolts
60S-2 P-Bar Production Beam Present in NuMI Kicker Gap I:BNKG X 65-6 JBE
SAT4
No P-Bar Production Beam Should Be Present Before NuMI Extraction 4 Volts NA 1.5 Volts NA 1.5 Volts NA
60S-3 Extraction Kicker PS Charging Waveform Buffered Reference I:KPS6NE X 65-12 BE
SAT2
Charging Waveform Buffered Refererence Nominal 50.001 kVolts Nom - 5% Nom + 5% 47.5 52.5 60 kVolts
60S-4 Extraction Kicker PS Available Voltage I:KPS6N X 65-13 BE
SAT2
Nominal Voltage 50.001 kVolts Nom - 5% Nom + 5% 47.5 52.5 60 kVolts
60S-5 Extraction Kicker PS Sampled Current I:KPS6NI X 65-14 AE
SAT3
Current Nominal 4,912 Amps Nom - 2% Nom + 2% 4,940 5,120 8,000 Amps
60S-6 Kicker Flourinert Cooling System Temperature Reference I:K6FTR X 65-15 Cont
SAT1
Temperature Reference Nominal 100 F 60 F 120 F 60 F 120 F 130 F
60S-7 Kicker Flourinert Cooling System Temperature Error I:K6FTE X 65-16 Cont
SAT1
Difference Between Actual and Set Point Nominal 0 F -5 F +5 F -5 F +5 F 70 F
60S-8 Kicker Flourinert Cooling System Filter/Return Temp I:K6FT2 X 65-18 Cont
SAT1
Filter/Return Temperature Nominal 100 F 60 F 120 F 60 F 120 F 216 F
60S "60S" Local 200 Module Inputs Near Top of Rack MI60124.    200 Module at CC $63 N22.
60S-9 PCI Permit from
MADC #65 
X 200-1 Now All Monitored Inputs Nominal 2 V+ into 100 Ohm NA NA NA NA NA
60S-10 NuMI Radiation               Safety System X 200-2 Now CDC Permit 2 V+ into 100 Ohm NA NA NA NA NA
60S-11 MI-52 P-Bar Production Batch Kicker System Related to
I:KPS5S
X 200-3 Now Kicker Power Supply Status OK 2 V+ into 100 Ohm NA NA NA NA NA
60S-12 NuMI Extraction Kicker Power Supply Related to
I:KPS6N
X 200-4 Now Kicker Power Supply Status OK 2 V+ into 100 Ohm NA NA NA NA NA
60S-13 No Beam in NuMI Kicker Gap Related to
I:BNKG
X 200-5 Now No P-Bar Production Beam Should Be Present ~0.5 msec Before NuMI Extraction at I:BNKGST 2 V+ into 100 Ohm NA NA NA NA NA
                           
60A "60A" C204 for MADC #44 at CC $70 N18.   SAT1 SAT3 SAT4 SAT5  Required Here.
60A-1 MI Horiz Intensity I:HI606N X 44-0 BJBE
SAT5
Enough Intensity to Give Valid BPM Values Beam Intensity Should be Greater than 1.0xE12/PP and Between Limits to Set the Internal Beam Present Flag 5,000 65,000 CNTS 
60A-2 Main Inj Loss Monitor Near Q612 for MI Beam Quality I:LMQ612 X 44-1 BJBE
SAT5
Acceptable Loss Nominal TBD
Alberto's Call
NA TBD NA 0.8 Volts Volts
60A-3 Trim Element PS
Bulk Voltage Out
I:CPS6NV X 44-2 Cont
SAT1
Voltage Nominal 175 Volts 150 Volts 190 Volts 150 Volts 190 Volts 200 Volts
60A-4 Loss Monitor Chassis #1 High Voltage Out E:LMHV1O X 44-3 Cont
SAT1
High Voltage Present 2,000 Volts 1,500 Volts 2,500 Volts 1,500 Volts 2,500 Volts 3,000 Volts
60A-5 Loss Monitor Chassis #1 High Voltage Return E:LMHV1R X 44-4 Cont
SAT1
High Voltage Present 2,000 Volts 1,500 Volts 2,500 Volts 1,500 Volts 2,500 Volts 3,000 Volts
60A-6 Loss Mon at KM602A I:LMNKMA X 44-5 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-7 Loss Mon at KM602B I:LMNKMB X 44-6 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-8 Loss Mon at KM602C I:LMNKMC X 44-7 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-9 Loss Mon at LAM60 I:LML60 X 44-8 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-10 Loss Mon at LAM61A I:LML61A X 44-9 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-11 Loss Mon at LAM61B I:LML61B X 44-10 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-12 Loss Mon at V100 E:LMV100 X 44-11 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-13 Loss Mon at Q101 E:LMQ101 X 44-12 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-14 Loss Mon at HV101-1 E:LM1011 X 44-13 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-15 Loss Mon at HV101-2 E:LM1012 X 44-14 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-16 Loss Mon at Q102 E:LMQ102 X 44-15 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-17 Loss Monitor Chassis #2 High Voltage Out E:LMHV2O X 44-16 Cont
SAT1
High Voltage Present 2,000 Volts 1,500 Volts 2,500 Volts 1,500 Volts 2,500 Volts 3,000 Volts
60A-18 Loss Monitor Chassis #2 High Voltage Return E:LMHV2R X 44-17 Cont
SAT1
High Voltage Present 2,000 Volts 1,500 Volts 2,500 Volts 1,500 Volts 2,500 Volts 3,000 Volts
60A-19 Loss Mon at HV101-3 E:LM1013 X 44-18 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-20 Loss Mon at HV101-4 E:LM1014 X 44-19 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-21 Loss Mon at HV101-5 E:LM1015 X 44-20 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-22 Loss Mon at Q103 E:LMQ103 X 44-21 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-23 Loss Mon at HV101-6 E:LM1016 X 44-22 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-24 Loss Mon at Q104 E:LMQ104 X 44-23 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-25 Loss Mon at HT104 E:LMHT04 X 44-24 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-26 Loss Mon at Q105 E:LMQ105 X 44-25 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-27 Loss Mon at Q106 E:LMQ106 X 44-26 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-28 Loss Mon at Q107 E:LMQ107 X 44-27 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
60A-29 MIQ Loss Monitor Chassis #6 High Voltage Out I:LMHV6O X 44-28 Cont
SAT1
High Voltage Present 2,000 Volts 1,500 Volts 2,500 Volts 1,500 Volts 2,500 Volts 3,000 Volts
60A-30 MIQ Loss Monitor Chassis #6 High Voltage Return I:LMHV6R X 44-29 Cont
SAT1
High Voltage Present 2,000 Volts 1,500 Volts 2,500 Volts 1,500 Volts 2,500 Volts 3,000 Volts
60A-31 Main Inj Loss Monitor Near Q608 for MI Beam Quality I:LMQ608 X 44-46 BJBE
SAT5
Acceptable Loss Nominal TBD
Alberto's Call
NA TBD NA 1.8 Volts Volts
60A-32 Upstream Beam Intensity Toroid E:TOR101 X 44-47 AE
SAT3
Below Maximum Maximum Set by NuMI Run Coordinator NA 23 E12 NA 23 E12 58.19 E12 ppp
60A-33 Main Injector Horizontal Beam Position for Orbit Verification I:HP606N X 44-54 BJBE
SAT5
Nominal Position
Before Extraction
+ 0.5 mm
But Intensity Sensitive
Nom -1.5mm Nom +1.5mm -1 mm +2 mm mm
(+/- 5V Signal)
60A-34 Main Injector Vertical Beam Position for Orbit Verification I:VP607N X 44-55 BJBE
SAT5
Nominal Position
Before Extraction
+ 4.25 mm Nom -1.5mm Nom +1.5mm +2.75 mm +5.75 mm mm
(+/- 5V Signal)
60A-35 Main Injector Horizontal Beam Position for Orbit Verification I:HP608N X 44-56 BJBE
SAT5
Nominal Position
Before Extraction
- 21.2 mm Nom -1.5mm Nom +1.5mm - 22.7 mm - 19.7 mm mm
(+/- 5V Signal)
60A-36 Main Injector Vertical Beam Position for Orbit Verification I:VP609N X 44-57 BJBE
SAT5
Nominal Position
Before Extraction
0.0 mm Nom -1.5mm Nom +1.5mm - 1.5 mm +1.5 mm mm
(+/- 5V Signal)
60A-37 Main Injector Intensity at V607 BPM I:VI607N X 44-60 JBE
SAT4
Below Some Maximum Where the Target is Safe Above 2 E13 NA Presently Equivalent to 2.35 E13 NA 19,250 67,100 CNTS
5V = 4 E13 
60A "60A" Local 200 Module Inputs Near Top of Rack MI60227.    200 Module at CC $70 N19.
60A-38 PCI Permit from               MADC #44   X   200-1 Now All Monitored Inputs Nominal 2 V+ into 100 Ohm NA NA NA NA NA
                           
60B "60B" C204 for MADC #38 at CC $73 N21.    Only SAT2 Required Here.
60B-1 LAM60 PS Reference I:LAM60F X 38-0 BE
SAT2
Current Reference Nominal 915.01 Amps Nom - 5% Nom + 5% 869.3 960.8 1,000 Amps
60B-2 LAM60 PS Current I:LAM60 X 38-1 BE
SAT2
Current Nominal  915.01 Amps Nom - 0.5% Nom + 0.5% 910.43 919.59 1,000 Amps
60B-3 LAM60 PS I Error I:LAM60E X 38-2 BE
SAT2
Current Error Nominal 0 Amps -2 Amps + 2 Amps -2 2 20 Amps
60B-4 LAM61 PS Reference I:LAM61F X 38-5 BE
SAT2
Current Reference Nominal 1,967 Amps Nom - 5% Nom + 5% 1868.65 2065.35 2,500 Amps
60B-5 LAM61 PS Current I:LAM61 X 38-6 BE
SAT2
Current Nominal  1,967 Amps Nom - 0.5% Nom + 0.5% 1,957.17 1,976.84 2,500 Amps
60B-6 LAM61 PS I Error I:LAM61E X 38-7 BE
SAT2
Current Error Nominal 0 Amps -2 Amps + 2 Amps -2 2 25 Amps
60B-7 V100 PS Reference E:V100F X 38-11 BE
SAT2
Current Reference Nominal 2,806 Amps Nom - 5% Nom + 5% 2665.7 2946.3 5,000 Amps
60B-8 V100 PS Current E:V100 X 38-12 BE
SAT2
Current Nominal  2,806 Amps Nom - 0.5% Nom + 0.5% 2791.97 2820.03 5,000 Amps
60B-9 V100 PS I Error  E:V100E X 38-13 BE
SAT2
Current Error Nominal 0 Amps -2 Amps + 2 Amps -2 2 50 Amps
60B-10 HV101 "B" PS  Reference E:HV01BF X 38-17 BE
SAT2
Current Reference Nominal TBD or
1,602.5 Amps
Nom - 5% Nom + 5% 1522.38 1682.63 1,750 Amps
60B-11 HV101 PS Current E:HV101 X 38-19 BE
SAT2
Current Nominal  1,602.5 Amps Nom - 1.4% Nom + 0.5% 1580 1610.51 1,750 Amps
60B-12 HV101 PS I Error E:HV101E X 38-20 BE
SAT2
Current Error Nominal 0 Amps -2 Amps + 2 Amps -2 2 20 Amps
60B-13 QD101 PS Reference E:QD101F X 38-27 BE
SAT2
Current Reference Nominal 56.25 Amps Nom - 5% Nom + 5% 53.44 59.06 100 Amps
60B-14 QD101 PS Current E:QD101 X 38-28 BE
SAT2
Current Nominal  56.25 Amps Nom - 2% Nom + 2% 55.13 57.38 100 Amps
60B-15 QF102 PS Reference E:QF102F X 38-31 BE
SAT2
Current Reference Nominal 64.63 Amps Nom - 5% Nom + 5% 61.4 67.86 100 Amps
60B-16 QF102 PS Current E:QF102 X 38-32 BE
SAT2
Current Nominal  64.63 Amps Nom - 2% Nom + 2% 63.34 65.92 100 Amps
60B-17 QD103 PS Reference E:QD103F X 38-35 BE
SAT2
Current Reference Nominal 63.57 Amps Nom - 5% Nom + 5% 60.39 66.75 100 Amps
60B-18 QD103 PS Current E:QD103 X 38-36 BE
SAT2
Current Nominal  63.57 Amps Nom - 2% Nom + 2% 62.3 64.84 100 Amps
60B-19 QF104 PS Reference E:QF104F X 38-39 BE
SAT2
Current Reference Nominal 21.85 Amps Nom - 5% Nom + 5% 20.76 22.94 100 Amps
60B-20 QF104 PS Current E:QF104 X 38-40 BE
SAT2
Current Nominal  21.85 Amps Nom - 2% Nom + 2% 21.41 22.29 100 Amps
60B-21 QF105 PS Reference E:QF105F X 38-43 BE
SAT2
Current Reference Nominal 60.04 Amps Nom - 5% Nom + 5% 57.04 63.04 100 Amps
60B-22 QF105 PS Current E:QF105 X 38-44 BE
SAT2
Current Nominal  60.04 Amps Nom - 2% Nom + 2% 58.84 61.24 100 Amps
60B-23 QD106 PS Reference E:QD106F X 38-47 BE
SAT2
Current Reference Nominal 60.04 Amps Nom - 5% Nom + 5% 57.04 63.04 100 Amps
60B-24 QD106 PS Current E:QD106 X 38-48 BE
SAT2
Current Nominal  60.04 Amps Nom - 2% Nom + 2% 58.84 61.24 100 Amps
60B "60B" Local 200 Module Inputs Near Top of Rack MI60219.    200 Module at CC $73 N22.
60B-25 PCI Permit from
MADC #38 
X 200-1 Now All Monitored Inputs Nominal 2 V+ into 100 Ohm NA NA NA NA NA
60B-26 LAM60 Power Supply Related to
I:LAM60
X 200-2 Now In Regulation 2 V+ into 100 Ohm NA NA NA NA NA
60B-27 LAM61 Power Supply Related to
I:LAM61
X 200-3 Now In Regulation 2 V+ into 100 Ohm NA NA NA NA NA
60B-28 V100 Power Supply Related to
E:V100
X 200-4 Now In Regulation 2 V+ into 100 Ohm NA NA NA NA NA
60B-29 HV101 Power Supply Related to
E:HV101
X 200-5 Now In Regulation 2 V+ into 100 Ohm NA NA NA NA NA
                           
62A "62A" C204 for MADC #79 at CC $6C N21.    SAT1 SAT2 SAT3 Required Here.
62A-1 Loss Monitor Chassis #3 High Voltage Out E:LMHV3O X 79-0 Cont
SAT1
High Voltage Present 2,000 Volts 1,500 Volts 2,500 Volts 1,500 Volts 2,500 Volts 3,000 Volts
62A-2 Loss Monitor Chassis #3 High Voltage Return E:LMHV3R X 79-1 Cont
SAT1
High Voltage Present 2,000 Volts 1,500 Volts 2,500 Volts 1,500 Volts 2,500 Volts 3,000 Volts
62A-3 Loss Mon at Q108 E:LMQ108 X 79-2 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
62A-4 Loss Mon at V108-1 E:LM1081 X 79-3 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
62A-5 Loss Mon at V108-2 E:LM1082 X 79-4 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
62A-6 Loss Mon at Q109 E:LMQ109 X 79-5 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
62A-7 Loss Mon at V108-3 E:LM1083 X 79-6 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
62A-8 Loss Mon at V108-4 E:LM1084 X 79-7 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
62A-9 Loss Mon at Q110 E:LMQ110 X 79-8 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
62A-10 Loss Mon at V108-5 E:LM1085 X 79-9 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
62A-11 Loss Mon at V108-6 E:LM1086 X 79-10 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
62A-12 Loss Mon at Q111 E:LMQ111 X 79-11 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
62A-13 Loss Mon at Q112 E:LMQ112 X 79-12 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
62A-14 NuMI Stub Total LM E:TLMNS X 79-13 AE
SAT3
Acceptable Loss Nominal TBD NA 10 Rad/Sec NA 10 Rad/Sec 1746 Rad/Sec
62A-15 Upper Hobbit Total LM E:TLMCTU X 79-14 AE
SAT3
Acceptable Loss Nominal TBD NA 10 Rad/Sec NA 30 Rad/Sec 1746 Rad/Sec
62A-16 Lower Hobbit Total LM E:TLMCTD X 79-15 AE
SAT3
Acceptable Loss Nominal TBD NA 10 Rad/Sec NA 30 Rad/Sec 1746 Rad/Sec
62A-17 Pre-Target Total LM E:TLMPT X 79-16 AE
SAT3
Acceptable Loss Nominal TBD NA 10 Rad/Sec NA 10 Rad/Sec 1746 Rad/Sec
62A-18 Total Loss Monitors            High Voltage Out E:TLMHVO X 79-17 Cont
SAT1
High Voltage Present 800 Volts 700 Volts 900 Volts 700 Volts 900 Volts 3,000 Volts
62A-19 Total Loss Monitors            High Voltage Return E:TLMHVR X 79-18 Cont
SAT1
High Voltage Present 800 Volts 700 Volts 900 Volts 700 Volts 900 Volts 3,000 Volts
62A-20 Loss Mon at Beginning of Big Beam Pipe E:LMBBBP X 79-19 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
62A-21 V108 PS Reference E:V108F X 79-32 BE
SAT2
Current Reference Nominal 4,406.1 Amps Nom - 5% Nom + 5% 4,185.80 4,626.41 5,000 Amps
62A-22 V108 PS Current E:V108 X 79-33 BE
SAT2
Current Nominal  4,406.1 Amps Nom - 1.5% Nom + 1.5% 4,340.01 4,472.19 5,000 Amps
62A-23 V108 PS I Error E:V108E X 79-34 BE
SAT2
Current Error Nominal 0 Amps -2 Amps + 2 Amps -3 3 50 Amps
62A-24 QF107 PS Reference E:QF107F X 79-39 BE
SAT2
Current Reference Nominal 60.04 Amps Nom - 5% Nom + 5% 57.04 63.04 100 Amps
62A-25 QF107 PS Current E:QF107 X 79-40 BE
SAT2
Current Nominal  60.04 Amps Nom - 2% Nom + 2% 58.84 61.24 100 Amps
62A-26 QD108 PS Reference E:QD108F X 79-43 BE
SAT2
Current Reference Nominal 60.04 Amps Nom - 5% Nom + 5% 57.04 63.04 100 Amps
62A-27 QD108 PS Current E:QD108 X 79-44 BE
SAT2
Current Nominal  60.04 Amps Nom - 2% Nom + 2% 58.84 61.24 100 Amps
62A-28 QF109 PS Reference E:QF109F X 79-47 BE
SAT2
Current Reference Nominal 60.04 Amps Nom - 5% Nom + 5% 57.04 63.04 100 Amps
62A-29 QF109 PS Current E:QF109 X 79-48 BE
SAT2
Current Nominal  60.04 Amps Nom - 2% Nom + 2% 58.84 61.24 100 Amps
62A-30 QD110 PS Reference E:QD110F X 79-51 BE
SAT2
Current Reference Nominal 25.62 Amps Nom - 5% Nom + 5% 24.34 26.9 100 Amps
62A-31 QD110 PS Current E:QD110 X 79-52 BE
SAT2
Current Nominal  25.62 Amps Nom - 2% Nom + 2% 25.11 26.13 100 Amps
62A-32 QD111 PS Reference E:QD111F X 79-55 BE
SAT2
Current Reference Nominal 78.08 Amps Nom - 5% Nom + 5% 77.55 85.71 100 Amps
62A-33 QD111 PS Current E:QD111 X 79-56 BE
SAT2
Current Nominal  78.08 Amps Nom - 2% Nom + 2% 76.52 79.64 100 Amps
62A-34 QF112 PS Reference E:QF112F X 79-59 BE
SAT2
Current Reference Nominal 81.63 Amps Nom - 5% Nom + 5% 80 83.26 100 Amps
62A-35 QF112 PS Current E:QF112 X 79-60 BE
SAT2
Current Nominal  81.63 Amps Nom - 2% Nom + 2% 80 83.26 100 Amps
62A "62A" Local 200 Module Inputs Near Top of Rack MI62107.    200 Module at CC $6C N22.
62A-36 PCI Permit from               MADC #79 X 200-1 Now All Monitored Inputs Nominal 2 V+ into 100 Ohm NA NA NA NA NA
62A-37 V108 Power Supply X 200-2 Now In Regulation 2 V+ into 100 Ohm NA NA NA NA NA
62A-38 Sector
Isolation Valves
E:BV100
E:BV112A
E:BV112B
X 200-3 Now All Fully Open 2 V+ into 100 Ohm NA NA NA NA NA
62A-39 MI-62 LCW and Pond Water Systems Related to
E:62Winn and E:62Pinn
X   200-4 Now All Below
Monitored Inputs Nominal
2 V+ into 100 Ohm NA NA NA NA NA
62A-40 LCW Temperature E:62WTnn PLC Cont 97.5 F 90 F NA 105 F NA NA
62A-41 LCW Expansion Tank Level E:62WLnn PLC Cont Above 10 Inches 18 Inches 10 Inches NA NA NA
62A-42 LCW Pump Motors (2)              ON/OFF Status E:62WEnn PLC Cont One Pump Enabled to Run One ON and                        One OFF NA NA NA NA NA
62A-43 LCW Pump Motors (2) Current E:62WInn PLC Cont Enabled Motor Current Nominal FLA 75% FLA 125% FLA NA
62A-44 Pond Pump Motors (2)              ON/OFF Status E:62PEnn PLC Cont One Pump Enabled to Run One ON and                             One OFF NA NA NA NA NA
62A-45 Pond Pump Motors (2) Current E:62PInn PLC Cont Enabled Motor Current Nominal FLA 75% FLA 125% FLA NA
62A-46 Pressure Differential Across
Pond Pumps at PV-9
E:62PPnn PLC Cont Above Minimum 10 PSIG 2 PSIG NA NA NA
62A-47 LCW System Resistivity E:62WA08 PLC Cont Above Minimum 3 to 5 MOhm-cm 1 MOhm-cm NA 1 MOhm-cm NA NA
62A-48 LCW PLC Heartbeat X 200-5 Now Thump Thump 2 V+ into 100 Ohm NA NA NA NA NA
                           
65A "65A" C204 for MADC #85 at CC $E4 N21.    SAT1 SAT2 and SAT6 Required Here.
65A-1 Intensity from H121 BPM E:HI121P X 85-0 AE
SAT6
Enough Intensity to Give Valid BPM Values Beam Intensity Should be Greater than 1.0xE12/PP and Between Limits to Set the Internal Beam Present Flag 5,000 65,000 CNTS 
65A-2 V118 PS Current E:V118 X 85-3 BE
SAT2
Current Nominal  4,125.1 Amps Nom - 0.5% Nom + 0.5% 4104.47 4145.73 5,000 Amps
65A-3 V118 PS I Error E:V118E X 85-4 BE
SAT2
Current Error Nominal 0 Amps -2 Amps + 2 Amps -2 2 5 Amps
65A-4 V118 PS Reference E:V118F X 85-9 BE
SAT2
Current Reference Nominal 4,173.15 Amps Nom - 5% Nom + 5% 3918.85 4331.36 5,000 Amps
65A-5 QD113 PS Reference E:QD113F X 85-11 BE
SAT2
Current Reference Nominal 81.63 Amps Nom - 5% Nom + 5% 77.55 85.71 100 Amps
65A-6 QD113 PS Current E:QD113 X 85-12 BE
SAT2
Current Nominal  81.63 Amps Nom - 2% Nom + 2% 80 83.26 100 Amps
65A-7 QF114 PS Reference E:QF114F X 85-15 BE
SAT2
Current Reference Nominal 78.08 Amps Nom - 5% Nom + 5% 74.18 81.98 100 Amps
65A-8 QF114 PS Current E:QF114 X 85-16 BE
SAT2
Current Nominal  78.08 Amps Nom - 2% Nom + 2% 76.52 79.64 100 Amps
65A-9 QF115 PS Reference E:QF115F X 85-19 BE
SAT2
Current Reference Nominal 25.62 Amps Nom - 5% Nom + 5% 24.34 26.9 100 Amps
65A-10 QF115 PS Current E:QF115 X 85-20 BE
SAT2
Current Nominal  25.62 Amps Nom - 2% Nom + 2% 25.11 26.13 100 Amps
65A-11 QD116 PS Reference E:QD116F X 85-23 BE
SAT2
Current Reference Nominal 63.97 Amps Nom - 5% Nom + 5% 60.77 67.17 100 Amps
65A-12 QD116 PS Current E:QD116 X 85-24 BE
SAT2
Current Nominal  63.97 Amps Nom - 2% Nom + 2% 62.69 65.25 100 Amps
65A-13 QF117 PS Reference E:QF117F X 85-27 BE
SAT2
Current Reference Nominal 55.02 Amps Nom - 5% Nom + 5% 52.27 57.77 100 Amps
65A-14 QF117 PS Current E:QF117 X 85-28 BE
SAT2
Current Nominal  55.02 Amps Nom - 2% Nom + 2% 53.92 56.12 100 Amps
65A-15 QD118 PS Reference E:QD118F X 85-31 BE
SAT2
Current Reference Nominal 51.69 Amps Nom - 5% Nom + 5% 49.11 54.27 100 Amps
65A-16 QD118 PS Current E:QD118 X 85-32 BE
SAT2
Current Nominal  51.69 Amps Nom - 2% Nom + 2% 50.66 52.72 100 Amps
65A-17 QF119 PS Reference E:QF119F X 85-35 BE
SAT2
Current Reference Nominal 35.34 Amps Nom - 5% Nom + 5% 32.3 37.11 100 Amps
65A-18 QF119 PS Current E:QF119 X 85-36 BE
SAT2
Current Nominal  35.34 Amps Nom - 2% Nom + 2% 34.63 36.05 100 Amps
65A-19 QD120 PS Reference E:QD120F X 85-39 BE
SAT2
Current Reference Nominal 68.17 Amps Nom - 5% Nom + 5% 64.76 71.58 100 Amps
65A-20 QD120 PS Current E:QD120 X 85-40 BE
SAT2
Current Nominal  68.17 Amps Nom - 2% Nom + 2% 66.81 69.53 100 Amps
65A-21 QF121 PS Reference E:QF121F X 85-43 BE
SAT2
Current Reference Nominal 60.38 Amps Nom - 5% Nom + 5% 57.36 63.4 100 Amps
65A-22 QF121 PS Current E:QF121 X 85-44 BE
SAT2
Current Nominal  60.38 Amps Nom - 2% Nom + 2% 59.17 61.59 100 Amps
65A-23 H117 PS Reference E:H117F X 85-47 BE
SAT2
Current Reference Nominal 50 Amps Nom - 5% Nom + 5% 47.5 52.5 100 Amps
65A-24 H117 PS Current E:H117 X 85-48 BE
SAT2
Current Nominal  50 Amps Nom - 2% Nom + 2% 49 51 100 Amps
65A-25 Beam Position from H121 E:HP121P X 85-52 AE
SAT6
Nominal Position
+/- 1.5 mm
-1.2 mm -2.7 mm +0.3 mm -2.7 mm +0.3 mm 60 mm
65A-26 Beam Position from V121 E:VP121P X 85-53 AE
SAT6
Nominal Position
+/- 1.5 mm
1.0 mm -0.5 mm +2.5 mm -0.5 mm +2.5 mm 60 mm
65A-27 Beam Position from HTGT E:HPTGTP X 85-54 AE
SAT6
Nominal Position
+/- 1.5 mm
-1.2 mm -2.7 mm +0.3 mm -2.7 mm +0.3 mm 60 mm
65A-28 Beam Position from VTGT E:VPTGTP X 85-55 AE
SAT6
Nominal Position
+/- 1.5 mm
1.0 mm -0.5 mm +2.5 mm -0.5 mm +2.5 mm 60 mm
65A-29 Trim Element PS
Bulk Voltage Out
E:CPS65V X 85-56 Cont
SAT1
Voltage Nominal 175 Volts 150 Volts 190 Volts 150 Volts 190 Volts 200 Volts
65A-30 MI-65 BPM Functional Status / Heartbeat E:65BPMB X 85-57 BE
SAT2
Logic Low at Start of Flattop 0 Volts NA 2 Volts NA 2 Volts 10 Volts
65A-31 MI-65 BPM Functional Status / Heartbeat E:65BPMA X 85-58 AE
SAT6
Logic High After Extraction 5 Volts 2 Volts NA 2 Volts NA 10 Volts
65A "65A" Local 200 Module Inputs Near Top of Rack MI65103.  200 Module at CC $E4 N22.
65A-32 PCI Permit from               MADC #85 X 200-1 Now All Monitored Inputs Nominal 2 V+ into 100 Ohm NA NA NA NA NA
65A-33 V118 Power Supply Related to
E:V118
X 200-2 Now In Regulation 2 V+ into 100 Ohm NA NA NA NA NA
                           
THA "THA" C204 for MADC #87 at CC $E6 N19.      SAT1 SAT2 SAT3 SAT4 Required Here.
SAT4 Timing Presently Conditional.
THA-1 Horn Stripline Current E:HSLI X 87-0 JBE
SAT4
Before Extraction Nominal 200,000 Amps Nom - 2% Nom + 2% More Study Needed ??? Amps
THA-2 Horn Power Supply A Reference E:NHSAF X 87-1 BE
SAT2
Reference Nominal 614 Volts
Observed
Nom - 5% Nom + 5% 550 700 1,000 Volts
THA-3 Horn Power Supply B Reference E:NHSBF X 87-2 BE
SAT2
Reference Nominal Spare Not in Active Service 1,000 Volts
THA-4 Horn Power Supply A Slowed Reference E:NHSASF X 87-3 BE
SAT2
Slow Start                  Reference Nominal 604.5 Volts
Observed
Nom - 5% Nom + 5% 550 700 1,000 Volts
THA-5 Horn Power Supply B Slowed Reference E:NHSBSF X 87-4 BE
SAT2
Slow Start                  Reference Nominal Spare Not in Active Service 1,000 Volts
THA-6 Peak Horn Stripline Current E:HSLIP X 87-5 AE
SAT3
Peak Nominal 200,000 Amps Nom - 2% Nom + 2% More Study Needed ??? Amps
THA-7 Loss Monitor Chassis #4 High Voltage Out E:LMHV4O X 87-6 Cont
SAT1
High Voltage Present 2,000 Volts 1,500 Volts 2,500 Volts 1,500 Volts 2,500 Volts 3,000 Volts
THA-8 Loss Monitor Chassis #4 High Voltage Return E:LMHV4R X 87-7 Cont
SAT1
High Voltage Present 2,000 Volts 1,500 Volts 2,500 Volts 1,500 Volts 2,500 Volts 3,000 Volts
THA-9 Loss Mon at Q113 E:LMQ113 X 87-8 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 20 Rad/Sec 1746 Rad/Sec
THA-10 Loss Mon at Q114 E:LMQ114 X 87-9 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
THA-11 Loss Mon at Q115 E:LMQ115 X 87-10 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
THA-12 Loss Mon at Q116 E:LMQ116 X 87-11 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
THA-13 Loss Mon at Q117 E:LMQ117 X 87-12 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
THA-14 Loss Mon at H117 E:LMH117 X 87-13 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
THA-15 Loss Mon at Q118 E:LMQ118 X 87-14 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
THA-16 Loss Mon at V118-1 E:LM1181 X 87-15 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
THA-17 Loss Mon at V118-2 E:LM1182 X 87-16 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
THA-18 Loss Mon at Q119 E:LMQ119 X 87-17 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
THA-19 Baffle Temperature 1 E:BAFT1 X 87-34 Cont
SAT1
Below Extreme 18 C NA 76 C NA 60 Degrees C
THA-20 Baffle Temperature 2 E:BAFT2 X 87-35 Cont
SAT1
Below Extreme 18 C NA 76 C NA 60 Degrees C
THA-21 Targt Pile Fan Differential Pressure E:TPCFDP X 87-45 Cont
SAT1
Between Extremes 6.4 Inches H2O 4 Inches H2O 15 Inches H2O 4 Inches H2O 15 Inches H2O 25 Inches H2O
THA-22 Targt Pile Air Supply Temperature E:TPCAST X 87-46 Cont
SAT1
Between Extremes 18 C 12 C 26 C 12 C 26 C 100 C
THA-23 Target Helium Gas Flow - Rough E:TGTHFR X 87-52 Cont
SAT1
Below Nominal Zero NA 0.5 NA 1.4 6 Liter/Minute
THA-24 Arrival of Beam wrt Clock E:NOCLU1 X 87-61 AE Between Extremes Not Available
THA-25 Horn BDOT Zero wrt Clock E:NOCLU2 X 87-62 AE Between Extremes Not Available
THA-26 Beam Arvl - BDOT Zero E:NOCLU3 X 87-63 AE Between Extremes Not Available
THA "THA" Local 200 Module Inputs Near Top of Rack THSR103.  200 Module at CC $E6 N20.
THA-27 PCI Permit from               MADC #87 X 200-1 Now All Monitored Inputs Nominal 2 V+ into 100 Ohm NA NA NA NA NA
THA-28 THSR PLC Heartbeat X 200-2 Now Thump Thump 2 V+ into 100 Ohm NA NA NA NA NA
THA-29 Horn Power Supply A Related to
E:NHSA
X 200-3 Now Power Supply Ready    (Rectifiers On) 2 V+ into 100 Ohm NA NA NA NA NA
THA-30 Horn Power Supply B Related to
E:NHSB
X 200-4 Now Power Supply Ready    (Rectifiers On) 2 V+ into 100 Ohm NA NA Not in Active Service NA
THA-31 Target Hall (South) Air Damper Closed X   200-6 Now Air Damper Closed
(by DDC Operation)
2 V+ into 100 Ohm NA NA NA NA NA
                           
THB "THB" C204 for MADC #88 at CC $E6 N18.    SAT1 SAT3 Required Here.
THB-1 Loss Monitor Chassis #5 High Voltage Out E:LMHV5O X 88-0 Cont
SAT1
High Voltage Present 2,000 Volts 1,500 Volts 2,500 Volts 1,500 Volts 2,500 Volts 3,000 Volts
THB-2 Loss Monitor Chassis #5 High Voltage Return E:LMHV5R X 88-1 Cont
SAT1
High Voltage Present 2,000 Volts 1,500 Volts 2,500 Volts 1,500 Volts 2,500 Volts 3,000 Volts
THB-3 Loss Mon at V118-3 E:LM1183 X 88-2 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
THB-4 Loss Mon at V118-4 E:LM1184 X 88-3 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
THB-5 Loss Mon at Q120 E:LMQ120 X 88-4 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
THB-6 Loss Mon at Q121 E:LMQ121 X 88-5 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
THB-7 Loss Mon Before TORTGT Toroid E:LMTGTT X 88-8 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 50 Rad/Sec 1746 Rad/Sec
THB-8 Loss Mon at Target Shield Wall E:LMTSW X 88-9 AE
SAT3
Acceptable Loss Nominal TBD NA 5 Rad/Sec NA 5 Rad/Sec 1746 Rad/Sec
THB "THB" Local 200 Module Inputs Near Top of Rack THSR104.  200 Module at CC $E6 N21.
THB-9 PCI Permit from               MADC #88 X 200-1 Now All Monitored Inputs Nominal 2 V+ into 100 Ohm NA NA NA NA NA
THB-10 Target and Baffle
RAW Skid
Related to
E:TBRinn
X   200-2 Now All Below
Monitored Inputs Nominal
2 V+ into 100 Ohm NA NA NA NA NA
THB-11 Discharge Minus Suction Pressure E:TBRPnn PLC Cont Within Extremes TBD 5 PSIG 75 PSIG NA
THB-12 Supply Temperature E:TBRTnn PLC Cont Below Extreme 95 F NA 130 F NA NA
THB-13 Expansion Tank Level  E:TBRLnn PLC Cont Above 10 Inches 18 Inches 10 Inches NA NA NA
THB-14 Pump Motors (2)              ON/OFF Status E:TBREnn PLC Cont One Pump Enabled to Run One ON and                     One OFF NA NA NA NA NA
THB-15 Pump Motors (2) Current E:TBRInn PLC Cont Enabled Motor Current Nominal FLA 75% FLA 125% FLA NA
THB-16 Target Helium Pressure E:BTHP01 PLC Cont Positive Helium Pressure to Keep Water Out >21 PSIG 21 PSIG NA   NA NA
THB-17 Horn 1
RAW Skid
Related to
E:H1Rinn
X   200-3 Now All Below
Monitored Inputs Nominal
2 V+ into 100 Ohm NA NA NA NA NA
THB-18 Discharge Minus Suction Pressure E:H1RPnn PLC Cont Within Extremes 40 PSIG 5 PSIG 75 PSIG NA
THB-19 Supply Temperature E:H1RTnn PLC Cont Below Extreme 70 F NA 90 F NA NA
THB-20 Expansion Tank Level  E:H1RLnn PLC Cont Above 10 Inches 24 Inches 10 Inches NA NA NA
THB-21 Pump Motors (2)              ON/OFF Status E:H1REnn PLC Cont One Pump Enabled to Run One ON and                        One OFF NA NA NA NA NA
THB-22 Pump Motors (2) Current E:H1RInn PLC Cont Enabled Motor Current Nominal FLA 75% FLA 125% FLA     NA
THB-23 Horn 2
RAW Skid
Related to
E:H2Rinn
X PLC 200-4 Now All Below
Monitored Inputs Nominal
2 V+ into 100 Ohm NA NA NA NA NA
THB-24 Discharge Minus Suction Pressure E:H2RPnn PLC Cont Within Extremes 40 PSIG 5 PSIG 75 PSIG NA
THB-25 Supply Temperature E:H2RTnn PLC Cont Below Extreme 70 F NA 90 F NA NA
THB-26 Expansion Tank Level  E:H2RLnn PLC Cont Above 10 Inches 24 Inches 10 Inches NA NA NA
THB-27 Pump Motors (2)              ON/OFF Status E:H2REnn PLC Cont One Pump Enabled to Run One ON and                             One OFF NA NA NA NA NA
THB-28 Pump Motors (2) Current E:H2RInn PLC Cont Enabled Motor Current Nominal FLA 75% FLA 125% FLA     NA
THB-29 Decay Pipe Cooling
RAW Skid
Upstream End 
Related to
E:DURinn
X   200-5 Now All Below
Monitored Inputs Nominal
2 V+ into 100 Ohm NA NA NA NA NA
THB-30 Discharge Minus Suction Pressure E:DURPnn PLC Cont Within Extremes TBD 5 PSIG 75 PSIG NA
THB-31 Temperature E:DURTnn PLC Cont Below Extreme 70 F NA 105 F NA NA
THB-32 Expansion Tank Level  E:DURLnn PLC Cont Above 10 Inches 24 Inches 10 Inches NA NA NA
THB-33 Pump Motors (2)              ON/OFF Status E:DUREnn PLC Cont One Pump Enabled to Run One ON and                     One OFF NA NA NA NA NA
THB-34 Pump Motors (2) Current E:DURInn PLC Cont Enabled Motor Current Nominal FLA 75% FLA 125% FLA     NA
THB-35 Total Loss Monitor
Gas Flow
(E:TLMGF) X   200-6 Now Gas Flowing 2 V+ into 100 Ohm NA NA NA NA NA
THB-36 Target & Baffle RAW Flow (E:TBR...) X 200-7 Now RAW Flowing 2 V+ into 100 Ohm NA NA NA NA NA
                           
MSB "MSB" Local 200 Module Inputs Near Top of Rack MSB101.  200 Module at CC $E7 N22.
  No Permits are Connected at this Location.  All Inputs Jumpered to Current Source.
                           
MND "MND" Local 200 Module Inputs Near Top of Rack MND101.  200 Module at CC $E8 N22.
  No Permits are Connected at this Location.  All Inputs Jumpered to Current Source.
                           
AAT "AAT" Local 200 Module Inputs Near Top of Rack AAT103.  200 Module at CC $E9 N22.
AAT-1 Absorber Cooling
RAW Skid
Related to
E:ABRinn
X PLC 200-1 Now All Below
Monitored Inputs Nominal
2 V+ into 100 Ohm NA NA NA NA NA
AAT-2 Discharge Minus Suction Pressure E:ABRPnn PLC Cont Within Extremes 20 PSIG 5 PSIG 50 PSIG NA
AAT-3 Supply Temperature E:ABRTnn PLC Cont Below Extreme 100 F NA 110 F NA NA
AAT-4 Expansion Tank Level  E:ABRLnn PLC Cont Above 10 Inches 18 Inches 10 Inches NA NA NA
AAT-5 Pump Motors (2)              ON/OFF Status E:ABREnn PLC Cont One Pump Enabled to Run One ON and                    One OFF NA NA NA NA NA
AAT-6 Pump Motors (2) Current E:ABRInn PLC Cont Enabled Motor Current Nominal FLA 75% FLA 125% FLA     NA
AAT-7 Absorber Intermediate Cooling System Related to
E:ABIinn
X   200-2 Now All Below
Monitored Inputs Nominal
2 V+ into 100 Ohm NA NA NA NA NA
AAT-8 Expansion Tank Level  E:ABILnn PLC Cont Above 10 Inches 18 Inches 10 Inches NA NA NA
AAT-9 Pump Motors (2)              ON/OFF Status E:ABIEnn PLC Cont One Pump Enabled to Run One ON and                     One OFF NA NA NA NA NA
AAT-10 Pump Motors (2) Current E:ABIInn PLC Cont Enabled Motor Current Nominal FLA 75% FLA 125% FLA     NA
AAT-11 Decay Pipe Cooling RAW Skid - Downstream End Related to
E:DDRinn
X   200-3 Now All Below
Monitored Inputs Nominal
2 V+ into 100 Ohm NA NA NA NA NA
AAT-12 Discharge Minus Suction Pressure E:DDRPnn PLC Cont Within Extremes 120 PSIG 50 PSIG 150 PSIG Now Set to
40 PSIG
NA
AAT-13 Temperature E:DDRTnn PLC Cont Below Extreme 70 F NA 105 F NA NA
AAT-14 Pump Motors (2)              ON/OFF Status E:DDREnn PLC Cont One Pump Enabled to Run One ON and                       One OFF NA NA NA NA NA
AAT-15 Pump Motors (2) Current E:DDRInn PLC Cont Enabled Motor Current Nominal FLA 75% FLA 125% FLA     NA
AAT-16 Absorber Instrumentation  Related to
E:ABSinn
X   200-4 Now System Nominal 2 V+ into 100 Ohm NA NA NA NA NA
AAT-17 Various Absorber Thermocouples E:ABSTnn PLC Cont Each of the Four Thermocouples Must be Below Extreme 140 F NA 150 F NA   NA
AAT-18 AAT PLC Heartbeat   X   200-5 Now Thump Thump 2 V+ into 100 Ohm NA NA NA NA NA
AAT-19 MINOS AAT Elephant Door Air Damper Closed X   200-6 Now Air Damper Closed
(by DDC Operation)
2 V+ into 100 Ohm NA NA NA NA NA
                           
NuMI SAT Assignments Location Used SAT RESET TCLK Event
Sequence
Sample Time Delay Comment
SAT1 = Continuous 60S 60A 62A 65A THA THB $A5 $0F $0F $0F $0F Direct NA 5 Hz Rate Synchronized to $A5
SAT2 = Before Extraction 60S 60B 62A 65A THA $26 $A5 $25 Direct NA Sample at Beginning of Flattop
SAT3 = After Extraction 60S 60A 62A THA THB $A5 $A9 TD0 6 msec Happens Only if MIBS $74 is Issued
SAT4 = Just Before NuMI Extraction
but After P-Bar Extraction
60S $26 $A5 $25 TD1 48.9 msec At 60S, Mainly Checking I:BNKG Just After P-Bar Beam is Out.  The Setting for TD1 is Quite Critical Here.
Just Missed the Kicker Fire when at 49 msec.
SAT4 = Just Before NuMI Extraction
During a NuMI Only Cycle
60A $80 $A5 $25 TD1 40 msec At 60A, Mainly Checking I:VI607N Against a Maximum So the Target is Not Hit with Too Much Beam.
SAT4 = Just Before Extraction THA $26 $A5 $25 TD1 40 msec Expect Time Delay to be Adjusted Here
SAT5 = Beam Cycle Just Before NuMI Extraction but After P-Bar Extraction 60A $26 $A5 $25 TD2 48.3 msec Mainly Checking MI Loss Monitors and Position of MI Beam Before Extraction for Orbit Verifier Function.
SAT6 = Beam Cycle After Extraction 65A $A5 $19 $25 $A9 TD3 100 msec Some Extra Time Needed for BPM Electronics to Compute Intensity and Positions After a Shot.
Infrastructure Requirements for NuMI Beam Permit Current Important Timing Information
INFR-1 MINOS Service Building Fiber Optic Repeater and CAMAC Crate $E7 Equipment Operational Event Time Scale
INFR-2 Absorber Access Tunel Fiber Optic Repeater and CAMAC Crate $E9 Equipment Operational $A5 0 sec
INFR-3 Near Detector Hall Fiber Optic Repeater and CAMAC Crate $E8 Equipment Operational $25 1.190924 sec
INFR-4 MI-12 Service Building Fiber Optic Repeater Equipment Operational MIBS $79 (TCLK $81) 1.239022 sec
INFR-5 MI-62 Service Building Fiber Optic Repeater and CAMAC Crate $6C Equipment Operational MIBS $74 (TCLK $A9) 1.240074 sec
INFR-6 Target Hall Support Room Fiber Optic Repeater and CAMAC Crate $E6 Equipment Operational P-Bar Kicker Delay 24.87415 MI Rev
INFR-7 MI-65 Service Building Fiber Optic Repeater and CAMAC Crate $E4 Equipment Operational NuMI Kicker Delay 19.903061 MI Rev
INFR-8 MI-60 SB North Fiber Optic Repeater and CAMAC Crates $70 and $73 Equipment Operational NuMI Kicker Delay Approx 200 micro sec
INFR-9 MI-60 SB South Fiber Optic Repeater and CAMAC Crate $63 Equipment Operational $25 to MIBS $79 48.096 milli sec
INFR-10 Cross Gallery MAC Room Repeater Equipment Operational $25 to MIBS $74 49.15 milli sec
MIBS $79 to MIBS $74 1.052 milli sec